Draper SC1 Bedienerhandbuch Seite 23

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 120
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 22
DIN-Rail Transformer—DR-120
®
Features:
- AC input range selectable by switch
- Protections: Short circuit/Overload/Over voltage/Over temperature
- Cooking by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- UL 508 (industrial control equipment) approved
- LED indicator for power on
- 100% full load burn-in test
- Fixed switching frequency at 55KHz
- 3 years warranty
SPECIFICATION
MODEL DR-120-24
DC Voltage 24V
Rated Current 5A
Current Range 0 – 5A
Rated Power 120W
Ripple & Noise (max.) Note 2. 60mVp-p
OUTPUT Voltage Adj. Range 24 – 28V
Voltage Tolerance Note 3. ±1.0%
Line Regulation ±0.5%
Load Regulation ±1.0%
Set Up, Rise Time
Hold-Up Time (Ty.) 36ms/230VAC 32ms/115VAC at full load
Voltage Range 88 – 123VAC/176-264VAC by switch 248-370VDC
Frequency Range 47 – 63 Hz
INPUT Effi ciency (Typ.) 64%
AC Current (Typ.) 2.6A/115VAC 1.6A/230VAC
Inrush Current (Typ.) Cold Start 20A/115VAC 40A/230VAC
Leakage Current <3.5mA/240VAC
Overload
105 – 150% rated output power
Protection type: Constant current limiting, recovers
Automatically after fault condition is removed
PROTECTION Over Voltage
29-33V
Protection type: Shut down o/p voltage, re-power on to recover
Over Temperature
90°C±5°C(TSW1)
Protection type: shut down o/p voltage, recovers automatically
After temperature goes down
Working Temp. -10 – 60+C (refer to output load deraling curve
Working Humidity 20 – 90% RH non-condensing
ENVIRONMENT Storage Temp. Humidity -20 - +65C, 10 – 95% RM
Temp, Coeffi cient ±0.03%/C (0-50°C)
Vibration
10 – 500Hz, 2G 10min./1cycle.60min.each along X, Y, Z axes;
Mounting Compliance to IEC60068-2-6
Safety Standards UL508, UL60950-1, TUV EN60950-1 approved
Withstand Voltage !/P-O/P.3KVAC I/P-FG.1.5KVAC 0/P-FG.0.5KVAC
SAFETY & Isolation Resistance I/P-O/:, I/P-FG, O/P-FG:100M Ohms/500VDC
EMC (Note 4.) EMI Conduction & Radiator Compliance to EN55011, EN55022, (CISPR22) Class B
Harmonic Current Compliance to EN61000-3-2,-3
EMS Immunity
Compliance to EN61000-4,2,3,4,5,6,8,11, ENV50204, EN55024,
EN61000-6-2 (EN50082-2), heavy industry level, criteria A
MTBF 136.8Khrs.min. MIL-HDBK-217F (25°C)
OTHERS Dimension 65.5 x 125.2 x 100 mm (W x H x D)
Packing 0.78Kg; 20pcs/16.5Kg/1,29CUFT
NOTE: All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature.
Ripple & noise are measure at 20MHz of bandwidth by using a 10” twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
Tolerance: includes set up tolerance, fi re regulation and load regulation.
The power supply is considered a component which will be installed into a fi nal equipment. The fi nal equipment must be reconfi rmed that it still
meets EMC directives.
Page 23 of 120
Seitenansicht 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 119 120

Kommentare zu diesen Handbüchern

Keine Kommentare