DIN-RailTransformer—DR-480S
®
Features:
- AC input range selectable by switch
- Built in passive PFC function compliance to EN61000-3-2
- High-effi ciency 89% and low dissipation
- Protections: Short circuit/Over Load/Over voltage/Over temperature
- Cooling by free air convection
- Built-in constant current limiting circuit
- Can be installed on DIN rail TS-35/7.5 or 15
- UL 508 (industrial control equipment) approved
- EN61000-6-2(EN50082-2) industrial immunity level
- 100% full load burn-in test
- 3 years warranty
SPECIFICATION
MODEL DRP480S-24
DC Voltage 24V
Rated Current 20A
Current Range 0 – 20A
Rated Power 480W
Ripple & Noise (max.) Note 2. 120mVp-p
OUTPUT Voltage Adj. Range 24 – 28V
Voltage Tolerance Note 3. ±1.0%
Line Regulation ±0.5%
Load Regulation ±1.0%
Set Up, Rise Time 1200ms, 40ms/230VAC,115VAC at full load
Hold-Up Time (Ty.) 23ms/230VAC, 115VAC at full load
Voltage Range Note 5. 90 – 132VAC/180 264VAC by switch 254-370FDC
Frequency Range 47 – 63 Hz
Power Factor (Typ.) 0.7/230VAC only
INPUT Effi ciency (Typ.) 89%
AC Current (Typ.) 8A/115VAC 3.2A/230VAC
Inrush Current (Typ.) Cold Start 27A/115VAC 45A/230VAC
Leakage Current <3.5mA/240VAC
Overload
105 – 150% rated output power
Protection type: Constant current limiting, recovers
automatically after fault condition is removed
PROTECTION Over Voltage
30 – 36V
Protection type: Shut down o/p voltage, re-power on to recover
Over Temperature
100°C±5°C(TSW: detect on heat sink of power switch
Protection type: shut down o/p voltage, recovers automatically
after temperature goes down
Working Temp. -20 – +70°C (refer to output load derating curve)
Working Humidity 20 – 90% RH non-condensing
ENVIRONMENT Storage Temp. Humidity -40 - +85°C, 10 – 95% RH
Temp, Coeffi cient ±0.03%/C (0-50°C)
Vibration
Component 10 – 500Hz, 2G 10min./.1cycle.60min.each along X, Y, Z axes; Mounting
Compliance to IEC60068-2-6
Safety Standards UL508, UL60950-1, TUV EN60950-1 approved
Withstand Voltage !/P-O/P.3KVAC I/P-FG.1.5KVAC 0/P-FG.0.5KVAC
SAFETY & Isolation Resistance I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
EMC (Note 4.) EMI Conduction & Radiation Compliance to EN55011, EN55022, (CISPR22) Class B
Harmonic Current Compliance to EN61000-3-2,-3
EMS Immunity
Compliance to EN61000-4,2,3,4,5,6,8,11, ENV50204, EN61204-3,
EN61000-6-2 (EN50082-2), heavy industry level, criteria A
MTBF 187.9Khrs.min. MIL-HDBK-217F (25°C)
OTHERS Dimension 227°125.2°100mm(W”H”D”)
Packing 2.60Kg; 6pcs/16.6Kg/1.75CUFT
NOTE: All parameters NOT specially mentioned are measured at 230VAC input, rated
load and 25°C of ambient temperature.
Ripple & noise are measure at 20MHz of bandwidth by using a 10” twisted pair-
wire terminated with a 0.1uf & 47uf parallel capacitor.
Tolerance: includes set up tolerance, fi re regulation and load regulation.
The power supply is considered a component which will be installed into a fi nal
equipment.
The fi nal equipment must be reconfi rmed that it still meets EMC directives.
Page 27 of 120