SUN AND WIND SENSOR V1.l and SUN SENSOR SWITCH V4 by Draper Page 4 of 9
Defaults:
Sun sensor timing = 10 minutes, low sunrise at 68 with increment of 3, low sunset at 48 with increment of 3. User
level selection is allowed and is set to high, Summer and Winter Actions =No Intermediate Positions on Sun (as
shown in "Sun Intermediate Stops"), Sun Sensor not disabled via a channel, No channel to switch between
Summer & Winter, Sun Sensor always uses Summer Actions.
Sun Intermediate Stops
No Intermediate Positions on Sun, use default settings (S+7+7 > C# > C10 > 01):
When the "high" LED on the Sun Sensor Switch display blinks, then the sunrise event is pending. When the selected
delay time expires, Close ALL will be sent. The sunrise event has then happened and the high LED will stop
blinking.
When the "low" LED on the Sun Sensor Switch display blinks, then the sunset event is pending. After the delay time,
Open ALL will be sent. The sunset event has then happened and the low LED will stop blinking.
Other levels of sun will display appropriately with no bus commands.
The user may adjust all levels up or down using the Sun Sensor Switch.
One Intermediate Position on Sun (S+7+7 > C# > C10 > 02):
If it was dark and is getting brighter (motor assumed open), and the "medium" LED on the Sun Sensor Switch
display blinks, then the 1" position sunrise event is pending. When the selected delay time expires, Open23 will be
sent. This sunrise event is then finished and the LED will stop blinking.
When the "hgh" LED on the Sun Sensor Switch display blinks, then the full sunrise event is pending. After the delay
time, Close ALL will be sent. The sunrise event has then finished and the high LED will stop blinking.
As it gets darker, the "medium" LED on the Sun Sensor Switch display will blink. This indicates the 1st position
sunset event is pending.
After the delay time, Open23 will be sent and the LED will stop blinking.
When the "low" LED on the Sun Sensor Switch display blinks, then the full sunset event is pending. After the delay
time, Open ALL will be sent and the low LED will stop blinking.
Other levels of sun will display appropriately with no bus commands.
The user may adjust all levels up or down using the Sun Sensor Switch.
Two Intermediate Positions on Sun, use default settings (S+7+7 > C# > C10 103):